Title: Effect of Loop Configuration on Steam Drum Level Control for a Multiple Drum Interconnected Loops Pressure Tube Type Boiling Water Reactor
Authors: GAIKWAD, AJ
VIJAYAN, PK
IYER, K
BHARTIYA, S
KUMAR, R
LELE, HG
GHOSH, AK
KUSHWAHA, HS
SINHA, RK
Keywords: model-predictive control
phase natural circulation
control-system
dynamic simulation
4-tank system
boiler model
power-plant
design
transient
performance
Issue Date: 2009
Publisher: IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Citation: IEEE TRANSACTIONS ON NUCLEAR SCIENCE, 56(6), 3712-3725
Abstract: For AHWR (Advanced Heavy Water Reactor), a pressure tube type Boiling Water Reactor (BWR) with parallel inter-connected loops, the Steam Drum (SD) level control is closely related to Main Heat Transport (MHT) coolant inventory and sustained heat removal through natural circulation, hence overall safety of the power plant. The MHT configuration with multiple (four) interconnected loops influences the SD level control in a manner which has not been previously addressed. The MHT configuration has been chosen based on comprehensive overall design requirements and certain Postulated Initiated Event (PIEs) for Loss of Coolant Accident (LOCA), which postulates a double ended break in the four partitioned Emergency Core Cooling System (ECCS) header. A conventional individual three-element SD level controller can not account for the highly coupled and interacting behaviors, of the four SD levels. An innovative three-element SD level control scheme is proposed to overcome this situation. The response obtained for a variety of unsymmetrical disturbances shows that the SD levels do not diverge and quickly settle to the various new set points assigned. The proposed scheme also leads to enhanced safety margins for most of the PIEs considered with a little influence on the 100% full power steady-state design conditions.
URI: http://dx.doi.org/10.1109/TNS.2009.2033682
http://dspace.library.iitb.ac.in/xmlui/handle/10054/8309
http://hdl.handle.net/10054/8309
ISSN: 0018-9499
Appears in Collections:Article

Files in This Item:

File SizeFormat
Effect of Loop Configuration on Steam .pdf2.56 MBAdobe PDFView/Open
View Statistics

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Valid XHTML 1.0! DSpace Software Copyright © 2002-2010  Duraspace - Feedback