| Title: | Analytical Description of the Load-Loss Asymmetry Phenomenon in Three-Phase Three-Limb Transformers |
| Authors: | ESCARELA-PEREZ, R KULKARNI, SV ALVAREZ-RAMIREZ, J KAUSHIK, K |
| Keywords: | cuts |
| Issue Date: | 2009 |
| Publisher: | IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC |
| Citation: | IEEE TRANSACTIONS ON POWER DELIVERY, 24(2), 695-702 |
| Abstract: | The asymmetry phenomenon observed during the load-loss test of three-phase transformers is rigorously analyzed. The transformer is represented as a three-port impedance network despite its six-port network nature, making any formal study more tractable. The analytical restrictions required for such a representation are derived. As a result, it is possible to mathematically prove (and understand) the asymmetrical behavior of a three-phase transformer subjected to the load-loss test. Only two circuit-field simulations or tests (single-phase load-loss tests) are required to obtain the impedance system of the six-winding transformer. A 3-D finite-element (FE) model of a transformer is used here to obtain its short-circuit impedances, exemplifying the use and extent of the analytical results. The eddy currents generated at the transformer tank and frame are properly taken into consideration. The short-circuit impedance model is validated with the 3-D FE model and with a six-port network approach that has been previously verified. |
| URI: | http://dx.doi.org/10.1109/TPWRD.2008.923988 http://dspace.library.iitb.ac.in/xmlui/handle/10054/8235 http://hdl.handle.net/10054/8235 |
| ISSN: | 0885-8977 |
| Appears in Collections: | Article
|
Files in This Item:
There are no files associated with this item.
|
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.
|