DSpace
 

DSpace at IIT Bombay >
IITB Publications >
Article >

Please use this identifier to cite or link to this item: http://dspace.library.iitb.ac.in/jspui/handle/10054/8235

Title: Analytical Description of the Load-Loss Asymmetry Phenomenon in Three-Phase Three-Limb Transformers
Authors: ESCARELA-PEREZ, R
KULKARNI, SV
ALVAREZ-RAMIREZ, J
KAUSHIK, K
Keywords: cuts
Issue Date: 2009
Publisher: IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Citation: IEEE TRANSACTIONS ON POWER DELIVERY, 24(2), 695-702
Abstract: The asymmetry phenomenon observed during the load-loss test of three-phase transformers is rigorously analyzed. The transformer is represented as a three-port impedance network despite its six-port network nature, making any formal study more tractable. The analytical restrictions required for such a representation are derived. As a result, it is possible to mathematically prove (and understand) the asymmetrical behavior of a three-phase transformer subjected to the load-loss test. Only two circuit-field simulations or tests (single-phase load-loss tests) are required to obtain the impedance system of the six-winding transformer. A 3-D finite-element (FE) model of a transformer is used here to obtain its short-circuit impedances, exemplifying the use and extent of the analytical results. The eddy currents generated at the transformer tank and frame are properly taken into consideration. The short-circuit impedance model is validated with the 3-D FE model and with a six-port network approach that has been previously verified.
URI: http://dx.doi.org/10.1109/TPWRD.2008.923988
http://dspace.library.iitb.ac.in/xmlui/handle/10054/8235
http://hdl.handle.net/10054/8235
ISSN: 0885-8977
Appears in Collections:Article

Files in This Item:

File SizeFormat
Analytical Description of the Load.pdf795.78 kBAdobe PDFView/Open
View Statistics

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Valid XHTML 1.0! DSpace Software Copyright © 2002-2010  Duraspace - Feedback