Title: Experimental evaluation of current transformer performance under saturation
Authors: CHAWANDE, PRADEEP
SOMAN, SA
APTE, PR
PANDIT, S
Keywords: current transformers
electrical faults
power transformer protection
Issue Date: 2005
Publisher: IEEE
Citation: Proceedings of the 7th International Power Engineering Conference, Singapore, 29 November- 2 December 2005, 1-5
Abstract: Current transformers form an integral part of protective systems. Ideal current transformers (CTs) are expected to reproduce the primary current faithfully on the secondary side. Often, during fault conditions an important component of current is exponentially decaying DC offset current. Under such conditions the CT saturates, and hence it cannot reproduce the primary current faithfully. This paper deals with experimental methods for determining CT performance under saturation. A laboratory setup has been developed to observe CT response under steady state and fault conditions. Thus, it is now possible to experimentally evaluate the CT performance under fault conditions.
URI: 10.1109/IPEC.2005.206882
http://hdl.handle.net/10054/379
http://dspace.library.iitb.ac.in/xmlui/handle/10054/379
ISBN: 981-05-5702-7
Appears in Collections:Proceedings papers

Files in This Item:

File Description SizeFormat
34152-2.pdf360.44 kBAdobe PDFView/Open
View Statistics

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Valid XHTML 1.0! DSpace Software Copyright © 2002-2010  Duraspace - Feedback